How much cooling and fresh air does an office need per person?

As a planning benchmark, a general open-plan office needs roughly 80 to 110 watts of cooling per square metre and around 10 litres per second of fresh air per person. Cellular offices sit lower, high-density spaces such as call centres sit higher, and server or comms rooms are a separate calculation entirely. Fresh air comes from Building Regulations Part F and CIBSE; cooling load depends on people, equipment, lighting and solar gain.

Office air conditioning units in a modern office ceiling

How much cooling does an office need?

Cooling load is the heat the system has to remove, and it is the sum of the people, the IT and equipment, the lighting and the solar gain through glazing. It is expressed in watts per square metre, and it varies with how the space is used. The figures below are planning benchmarks for sizing and feasibility, not a substitute for a room-by-room calculation.

Bright Modern Office Workspace
Modern office with cool fresh airflow from ceiling vents
Office type Typical cooling load Driver
Cellular / private office60 to 80 W/m²Lower occupancy and equipment density
General open-plan office80 to 110 W/m²Mixed people and IT load
High-density / call centre110 to 150 W/m²High headcount and equipment per m²
Meeting / conference roomSize by peak occupancyPeople gain dominates at full capacity
Server / comms roomSeparate dedicated calculationContinuous high equipment heat

Planning benchmarks for cooling load. A full design accounts for glazing orientation, occupancy and actual equipment.

People and IT drive it. Each occupant adds roughly 90 to 120 W of sensible heat, before their screens and the lighting, which is why headcount and equipment density move the figure more than floor area alone.

Sensible and latent heat: why both matter

Cooling has to deal with two kinds of heat. Sensible heat raises air temperature, from people, equipment, lighting and the sun, and it is what the watts-per-square-metre benchmark mostly captures. Latent heat is the moisture people and processes add, which the system also has to remove to keep the space comfortable. A space can be at the right temperature and still feel clammy if the latent load was ignored, which is why a full calculation separates the two rather than sizing on temperature alone.

How do I estimate the equipment load?

  • Start from the equipment that runs continuously: workstations, monitors, printers, network gear and any local servers.
  • Use realistic running power, not nameplate maximums, which overstate the steady load.
  • Apply a diversity allowance, because not everything draws peak power at the same moment.
  • Add any process or specialist equipment separately, and treat a comms rack as its own continuous load.

How much fresh air does an office need per person?

Fresh air is a ventilation requirement, set in Ireland by Building Regulations Part F and detailed in CIBSE guidance, and it is specified per person because it dilutes the carbon dioxide and pollutants people produce.

  • Around 10 litres per second per person is the common office design figure for good indoor air quality.
  • The outdoor air rate scales with occupancy, so a room's fresh air need rises as you add desks, independently of its cooling load.
  • Under-ventilation shows up as stuffiness, rising CO2 and afternoon drowsiness, even when the temperature is fine.

How is fresh air actually delivered?

Cooling and fresh air are related but not the same, and how the fresh air arrives affects both comfort and efficiency.

Method What it is Note
Natural ventilationOpenable windows and ventsSimple; uncontrolled in heat or cold
Mechanical ventilation with heat recovery (MVHR)Ducted supply/extract recovering heatFresh air without throwing away heating/cooling
Air handling unit (AHU)Central plant conditioning outdoor airLarger buildings; filters and tempers the air
Fan coil / VRF plus separate fresh airCooling units plus a dedicated fresh-air feedCooling and ventilation sized independently

Delivery methods for fresh air. Many comfort-cooling systems recirculate room air, so fresh air must be provided as well as cooling.

What about summer overheating and solar gain?

In summer, glazing can become the largest single load. Sun through a south- or west-facing window adds heat directly to the space, so two offices of identical size and headcount can have very different cooling needs purely from orientation and glazing. Shading, solar-control glass and blinds reduce the gain at source, which is often cheaper than sizing the cooling up to chase it. Any load assessment for an office with significant glazing should look at the worst-case summer condition, not just the average.

Will my existing plant support more people or equipment?

Adding headcount, IT or a server adds both heat and fresh-air demand, and existing plant has a fixed capacity. The quick test is whether the extra load stays within what the system was sized for. If you are planning office renovations or a change of layout, check the plant before the desks go in.

Change Existing plant usually supports? Watch for
A few more desks in an open-plan areaOften yesFresh air rate and local hot spots
Converting a store to a meeting roomSometimesPeak people load at full occupancy
Adding a small server or comms rackOften noNeeds dedicated cooling, runs 24/7
Dense call-centre fit-outUsually noBoth cooling load and fresh air jump
More glazing or a south-facing moveDependsSolar gain can dominate in summer

Indicative only. A load assessment confirms whether plant capacity, not just floor space, has room.

Cooling and ventilation plant also needs servicing to keep delivering its rated capacity. See how HVAC servicing fits into a planned preventative maintenance schedule.

Frequently asked questions

  • How much fresh air does an office need per person?
    Around 10 litres per second per person is the common office design figure for good indoor air quality, following Building Regulations Part F and CIBSE guidance. The total fresh air requirement rises with occupancy, so adding desks increases it.
  • How much cooling does an office need per square metre?
    A general open-plan office typically needs about 80 to 110 watts per square metre of cooling. Cellular offices are lower at roughly 60 to 80 W/m², and high-density spaces such as call centres can reach 110 to 150 W/m².
  • What is the difference between sensible and latent cooling load?
    Sensible load raises air temperature, from people, equipment, lighting and the sun. Latent load is the moisture people and processes add, which the system must also remove. A space can be the right temperature but still feel humid if the latent load was not accounted for.
  • Does a server room need separate cooling?
    Yes. Server and comms rooms carry continuous high equipment heat and run around the clock, so they need a dedicated cooling calculation and usually dedicated plant, rather than being folded into the office air conditioning.
  • Can my current air conditioning cope with more staff?
    A few extra desks often stay within capacity, but dense fit-outs, new meeting rooms and added IT frequently do not, because they raise both cooling load and fresh air demand. A load assessment confirms whether the plant, not just the floor space, has room.